Pump station Mixing group GM2F • The dual-function mixing group serves to lower and maintain the desired temperature of the heating agent of the surface heating system and to connects it with the high-parameter radiator system. Parameters: • static pressure (PN): max. 0.4 MPa (4 bar) • dynamic working pressure: max. 0.3 MPa (3 bar) • Kv: 1.9 m3/h • temperature regulation range: 20 - 40°C • accuracy of regulation: +/- 3°C The group includes:
• automatic pump • 3-way thermostatic mixing valve • automatic air vent with foot valve • thermometer • swivel drain valve • set of unions Advantages: • double-function - allows to connect radiator and floor manifolds into a single system • universal group for all manifolds with 210 mm bar spacing • accurate and easy to control • reversible
wireless adjustment of floor circuits
wireless regulation of battery circuits
hot domestic water solution