Direct start electronic control panel for 1 fire-fighting jockey pump according to European standard UNI  EN12845, specific and complete.

Control panel for 1 fire fighting jockey pump, D.O.L. start, European standard UNI EN 12845

A jockey pump is a small pump connected to a fire sprinkler system to maintain pressure in the sprinkler pipes. This is to ensure that if a fire-sprinkler is activated, there will be a pressure drop, which will be sensed by the fire pumps automatic controller, which will cause the fire pump to start.

Fire fighting jockey pumps power range

3-phase 400V max 0,55 -- 7.5 kW
3-phase 400V max 11kW
3-phase 400V max 15kW


Technical data:

  • Normally open input G/P1;
  • 3 inputs for unipolar level probes (COM-MIN-MAX);
  • Input T1 for motor clickson;
  • Normally open G.A. input for alarm activation;
  • AUTOMATIC-0-MANUAL buttons (unstable);
  • DIP-SWITCH 1 DIP-SWITCH 1 enable level alarm from probes;
  • DIP-SWITCH 2 selector thermal intervention delay 5/10 seconds;
  • DIP-SWITCH 3 setting alarm outputs;
  • DIP-SWITCH 4 DIP-SWITCH 4 enable alarm reset from motor clickswitch;
  • DIP-SWITCH 5 DIP-SWITCH 5 fill/drain operation;
  • DIP-SWITCH 6 selector enabling run/stop floats;
  • DIP-SWITCH 7 DIP-SWITCH 7 enable board activation delay from mains return;
  • Green mains presence/shortage or wrong phase sequence led;
  • Green LED automatic on;
  • Green motor active led;
  • Red LED level alarm from probes or A.G. input;
  • Red LED motor overload alarm / minimum current alarm;
  • Red motor overload / minimum current alarm; Red motor click alarm led;
  • Electronic maximum current control for overload with assisted calibration;
  • Electronic minimum current control for dry running with assisted calibration;
  • Automatic reset for minimum current alarm;
  • Auxiliary and motor protections with fuses;
  • Dry contact cumulative alarm output (COM-NO-NC resistive load - 5A / 250V);
  • Cumulative voltage alarm output (12Vdc / 100mA);
  • General block-door disconnector;
  • Predisposition for run capacitors for single-phase version (not included);
  • IP55 ABS box or metal box
  • Ambient temperature: -5/+40 °C;
  • Relative humidity 50% at 40 °C (non-condensing).