Jockey styrpanel för en brandpump, EN 12845

(bild för) Jockey styrpanel för en brandpump, EN 12845
Jockey styrpanel för en brandpump, EN 12845
(bild för) Jockey styrpanel för en brandpump, EN 12845
Jockey styrpanel för en brandpump, EN 12845
  • Modell: 014
  • Fraktvikt: 8 kg
  • Tillverkare: Elentek

Från: €699.00

Välj:

Hölje





Effekt













JOCKEY PUMP CONTROL PANEL
Direct start electronic control panel for 1 fire-fighting jockey pump according to European standard UNI  EN12845, specific and complete.

Control panel for 1 fire fighting jockey pump, D.O.L. start, European standard UNI EN 12845

A jockey pump is a small pump connected to a fire sprinkler system to maintain pressure in the sprinkler pipes. This is to ensure that if a fire-sprinkler is activated, there will be a pressure drop, which will be sensed by the fire pumps automatic controller, which will cause the fire pump to start.

Fire fighting jockey pumps power range

3-phase 400V max 0,55 -- 7.5 kW
3-phase 400V max 11kW
3-phase 400V max 15kW


Technical data:

  • Normally open input G/P1;
  • 3 inputs for unipolar level probes (COM-MIN-MAX);
  • Input T1 for motor clickson;
  • Normally open G.A. input for alarm activation;
  • AUTOMATIC-0-MANUAL buttons (unstable);
  • DIP-SWITCH 1 DIP-SWITCH 1 enable level alarm from probes;
  • DIP-SWITCH 2 selector thermal intervention delay 5/10 seconds;
  • DIP-SWITCH 3 setting alarm outputs;
  • DIP-SWITCH 4 DIP-SWITCH 4 enable alarm reset from motor clickswitch;
  • DIP-SWITCH 5 DIP-SWITCH 5 fill/drain operation;
  • DIP-SWITCH 6 selector enabling run/stop floats;
  • DIP-SWITCH 7 DIP-SWITCH 7 enable board activation delay from mains return;
  • Green mains presence/shortage or wrong phase sequence led;
  • Green LED automatic on;
  • Green motor active led;
  • Red LED level alarm from probes or A.G. input;
  • Red LED motor overload alarm / minimum current alarm;
  • Red motor overload / minimum current alarm; Red motor click alarm led;
  • Electronic maximum current control for overload with assisted calibration;
  • Electronic minimum current control for dry running with assisted calibration;
  • Automatic reset for minimum current alarm;
  • Auxiliary and motor protections with fuses;
  • Dry contact cumulative alarm output (COM-NO-NC resistive load - 5A / 250V);
  • Cumulative voltage alarm output (12Vdc / 100mA);
  • General block-door disconnector;
  • Predisposition for run capacitors for single-phase version (not included);
  • IP55 ABS box or metal box
  • Ambient temperature: -5/+40 °C;
  • Relative humidity 50% at 40 °C (non-condensing).