Drain1 400 V 3~fas 7.5kW, pumpstyrning

(bild för) Drain1 400 V 3~fas 7.5kW, pumpstyrning
Drain1 400 V 3~fas 7.5kW, pumpstyrning
(bild för) Drain1 400 V 3~fas 7.5kW, pumpstyrning
Drain1 400 V 3~fas 7.5kW, pumpstyrning
  • Modell: 01306
  • Fraktvikt: 10 kg
  • Tillverkare: Elentek

Från: €399.00  €276.10
Spara: 31% rabatt

Välj:

D. Tillbehör







Allmän bild
Float switch 10 m DROP 99036

Allmän bild
Kit 3 level probes 98007

Allmän bild
Ljus- och ljudlarm


Ideal for booster sets or for drainage pumps on sewage water lifting stations.
Control panel specific for drainage systems. The innovative switching power supply guarantees a working range with wide voltage variation supply to the electronic board making of Drain a reliable control panel in any situation.
• Complete range of control panels from 1 to 2 motors DOL start single-phase and three-phase
• Integrated and programmable dry running protection (by power factor or float switch)
• Control unit with phase sequence/failure and min-max voltage control
• Control unit with digital inputs (float switch)
• Integrated and programmable pumps rotation
• Multifunction LCD with multi-meter integrated and view of the status of the system
Technical features

  • Voltage 400 V 3∼
  • Power per pump 0.55-7.5 kW
  • Max current 16A
    GENERAL FEATURES
    Control unit with Liquid Crystal Display 2x16 line to
    visualize:
    • voltage
    • frequency
    • current
    • power factor (cosφ)
    • operating status of the system
    • system faults
    Controller: multilingual, sewage mode operation, digital
    ON-OFF input (float switches or external controls);
    Auxiliary users activation in case of fault of the user in
    operation (2 pumps models);
    Control of the users individually or in duty standby/assist (2 pumps models);
    Electronic control of motor overcurrent;
    Minimum voltage control : 180->415 (depending on the model);
    Max voltage control: 220->460 (depending on the model)
    Alarms control: dry running, motor in protection, motor
    overtemperature, board communication, voltage too low/ high, phase sequence/failure, min/max level;
    Alarms archive;
    Box in ABS IP55;
    Ambient temperature: -5/+40 °C;
    Relative humidity 50% a 40 °C (not condensed).

Copyright © 2026 profil.fi. Kontaktuppgifter och egen avhämtning
(bild för) Energiatukku